STANDARDS & FORMULAS

Shop Drawing for Cable Tray

Cable tray backbone and branches drawn on the plan, each segment’s width sized from the cables it carries.

Standards and regulations

  • IEC 60364-5-52
    Low-voltage installations - wiring systems

    The default: one layer, a diameter’s gap between neighbours (reference method F: the cables keep their full rating).

  • NEC 392.22
    Cable trays - number of conductors (fill)

    The “by area” option: the cables’ areas within a percentage of the tray’s (60 % by default here).

Formulas

Width (one layer, a diameter apart)

W = (Σ D + Σ gaps) × (1 + spare) → the next standard width

  • D = each cable’s outer diameter
  • gaps = one diameter between neighbours (the smaller cables’)
  • spare = 25 % by default; never under the minimum width

Fill

fill = Σ (π D² / 4) / (W × H)

  • H = the tray’s height

Design rules it applies

  • Width narrows after each branch, to fit what the backbone still carries from there
  • Checked against the fill limit (60 % by default)

For reference. MO.tool works these out to help your design; the engineer remains responsible for it. Always check the edition of each standard your project uses and the requirements of the local authority (DEWA, ADDC, Civil Defence…).