STANDARDS & FORMULAS

Shop Drawing for CCTV

CCTV cabling wired on the plan: conduit routed from the rack to every camera, nearest to nearest.

Standards and regulations

  • IEC 62676-4
    Video surveillance systems - application guidelines

    The camera count and cable the rack’s conduit is sized from.

Formulas

Conduit fill

fill = Σ (π d² / 4) / (π D² / 4) ≤ 40 %

  • d = each cable’s outer diameter
  • D = the conduit’s inside diameter

Design rules it applies

  • Conduit routed from the rack to the nearest camera, then the nearest one from there
  • Numbering CAM-01 on, matching the CCTV tool